Warranty: | 12 Months |
---|---|
Type: | Self-Starting Diesel Generator |
Installation Method: | Fixed |
Stroke: | Four Stroke |
Cooling Method: | Water Cooling |
Output Type: | AC Three Phase |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
THE FOLLOWING ENGINE, ALTERNATOR AND CONTROLLER BRANDS FOR OPTIONS
PRIME POWER | ENGINE | ALTERNATOR | CONTROLLER |
25KVA - 1500KVA | CUMMINS | STAMFORD | DEEPSEA |
9KVA - 2250KVA | PERKINS | GENLITEC | COMAP |
20KVA - 560KVA | DEUTZ | LEROY SOMER | SMARTGEN |
250KVA - 3000KVA | MTU | MECC ALTE | |
10KVA - 38KVA | KUBOTA | ENGGA | |
20KVA - 180KVA | LOVOL | MARATHON | |
150KVA - 750KVA | DOOSAN | ||
85KVA - 730KVA | VOLVO | ||
10KVA - 250KVA | RICARDO | ||
10KVA - 2500KVA | CATERPILLAR GENERATORS | ||
10KVA - 2500KVA | CHINESE BRAND |
Super Silent 100 KW Power Generator with Original Cummins Diesel Engine and ATS
Δ STANDARD CONFIGURATION
1) Powered by original CUMMINS water-cooled diesel engine.
2) Cummins diesel engine and Stamford alternator with global warranty.
3) STAMFORD Single bearing alternator with insulation class H and IP23.
4) Standard CHINT or DELIXI circuit breaker, ABB as an optional.
5) Steel base fuel tank with anti-vibration mounting.
6) Based at leaset 8 hours build-in fuel tank ensure daily use.
7) Industrial 9 dB muffler exhaust system, free-maintenance battery, complete set of user's manual.
8) Flexible fuel lines and lube oil, water & fuel drain cocks.
9) Standard SMARTGEN HGM420/HGM6110/HGM6120 antomatic start digital controller.
10) Original CUMMINS 50ºC full protection radiator.
10) Standard Shrink wrap packing method (Plywood packing box as optional).
Δ TESTING ITEMS
GENLITEC POWER provides a full line of brand new and high quality products.
Each and every unit is strictly factory tested before shipment.
1) Parts faults testing
2) Fuel tank pressure testing
3) Bolt tightening torque testing
4) Painting thickness testing
5) Voltage bearing and insulation testing
6) Noise testing
7) Loading Testing: 25%, 50%, 75%, 100%, 110% load to check verify that all control systems, alarm and shut-down protection.
Δ OPTIONAL SUPPLY
1) Weatherproof canopy / Soundproof canopy / Trailer-mounted
2) Engine / Alternator Pre-heaters
3) Auto load sharing & synchronization panel
4) Build-in ATS (Auto start & stop Main Failure (AMF)
5) Large 12/24 hours fuel tank
6) Power output sockets
Gensets model | GPC125(S) | |||||||
Prime power | 100KW | |||||||
Rated Voltage | 400/230V | |||||||
Rated frequency(HZ) | 50 | |||||||
Rated Speed | 1500rpm | |||||||
Power Factor | 0.8(lagging) | |||||||
Dimensions(mm) (L×W×H) | 2160×820×1300 | |||||||
Net Weight(kg) | 1200 | |||||||
2. Specification of diesel engine | ||||||||
Engine brand | Cummins | |||||||
Engine model | 6BTA5.9-G2 | |||||||
Number of Cylinders | 6 | |||||||
Cylinder arrangement | Vertical in-line | |||||||
Cycle | Four stroke | |||||||
Aspiration | Turbocharged after air-air cooled | |||||||
Bore×Stroke (mm×mm) | 102 x 120 | |||||||
Displacement (Liter) | 5.9 | |||||||
Compression Ratio | 17.5:1 | |||||||
Speed Governor | Electrical | |||||||
Cooling System | Water cooled | |||||||
Speed Stability (%) | ≤1% | |||||||
Total lubrication system capacity (L) | 16.4 | |||||||
Fuel Consumption at 100% Load (L/h) | 211 | |||||||
Starting Method | DC24V Electrical starting | |||||||
3. Specification of alternator | ||||||||
Alternator brand | GENLITEC (STAMFORD and LEROY SOMER as options) | |||||||
Alternator model | S274G100 | |||||||
Number of Phase | 3 | |||||||
Connecting Type | 3 Phase and 4 Wires | |||||||
Number of Bearing | 1 | |||||||
Protection Grade | IP21 | |||||||
Altitude | ≤1000m | |||||||
Exciter Type | Brushless ,Self-exciting, AVR automatic voltage regulating,100% Copper winding wire | |||||||
Insulation Class | H | |||||||
Telephone Influence Factor (TIF) | ≤50 | |||||||
THF | ≤2% | |||||||
Voltage Regulation, Steady State | ≤±1% | |||||||
Transient State Voltage | ≤-15%~+20% |
Suppliers with verified business licenses