Warranty: | 18 Months or 1200 Working Hours |
---|---|
Type: | Self-Starting Diesel Generator |
Installation Method: | Fixed |
Stroke: | Four Stroke |
Cooling Method: | Water Cooling |
Output Type: | AC Three Phase |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Δ STANDARD CONFIGURATION
GENSET MODEL | GPD225(S) |
Prime Power | 180KW/225KVA |
Standby Power | 200KW/250KVA |
Rated Voltage(V) | 400/230 |
Rated frequency(HZ) | 50 |
Rated Speed(RPM) | 1500 |
Power Factor | 0.8(lagging) |
Dimensions(mm) (L×W×H) | 2550x900x1750 (open type) |
Genset Weight(kg) | 1950 |
Dimensions(mm) (L×W×H) | 3300x1400x1950 (silent type) |
Genset Weight(kg) | 2900 |
DIESEL ENGINE SPECIFICATION | |
Engine model | BF6M1015-LAGA |
Standby Power | 231 kW/289 kVA |
Number of Cylinders | 6 |
Cylinder arrangement | V type |
Cycle | Four stroke |
Aspiration | Turbo |
Bore×Stroke (mm×mm) | 132 x 145 |
Displacement (Liter) | 11.9 |
Compression Ratio | 17.0:1 |
Speed Governor | Electrical |
Cooling System | Forced Water Cooling Cycle |
Total lubrication system capacity (L) | 38 |
Fuel Consumption at 100% Load (g/kw.h) | 212 |
Starting Method | DC24V electrical starting |
ALTERNATOR SPECIFICATION | |
Alternator brand | Stamford |
Alternator model | UCDI 274J |
Rated power | 180kW/225KVA |
Number of Phase | 3 |
Connecting Type | 3 Phase and 4 Wires |
Number of Bearing | 1 |
Protection Grade | IP23 |
Altitude | ≤1000m |
Exciter Type | Brushless ,Self-exciting, AVR automatic voltage regulating,100% Copper winding wire |
Insulation Class | H |
Telephone Influence Factor (TIF) | ≤50 |
THF | ≤2% |
Voltage Regulation, Steady State | ≤±1% |
Transient State Voltage | ≤-15%~+20% |
Suppliers with verified business licenses